Inhibited Transformer Oil INH-T2 20L

Category:

Description

Inhibited Transformer Oil INH-T2 – 20L (PCB-Free, Eskom Tested)
Greyhound INH-T2 is a high-purity inhibited transformer oil meeting IEC 60296:2020 (Inhibited). It provides 73 kV dielectric strength, −47 °C pour point and excellent oxidation stability for transformers and switchgear. The product is PCB-free and has been Eskom tested (meets Eskom required parameters; pending final Eskom Approval).
Where to use
Power & distribution transformers
Rectifiers, circuit breakers & switchgear
Electrical insulation/cooling applications
Why choose INH-T2
Premium virgin base stocks for long fluid life
Very low moisture on delivery (9 ppm typical)
Non-corrosive and PCB-free
Typical Physical Characteristics (TDS)
Property Units Test Methods Typical Data
Visual Appearance – – Clear, Pale
Kinematic Viscosity @ 40 °C mm²/s ISO 3104 8.2
Viscosity Index – ASTM D2270 115
Flash Point (COC) °C ISO 2719 178
Pour Point °C ISO 3016 −47
Density @ 20 °C kg/m³ ISO 12185 0.828
Breakdown Voltage (before treatment) kV IEC 60156 73
Dissipation Factor (DDF) @ 90 °C – IEC 61156 <0.11 Resistivity @ 90 °C TΩ·m IEC 60247 >10
Interfacial Tension mN/m ASTM D971 44
Acidity mg KOH/g IEC 62021 0.01
Inhibitor Content W% IEC 60666 0.4%
Aromatic Content % IEC 60590 12
PCB Content – IEC 61619 Not Detectable
Corrosive Copper – ASTM D1275 Pass
Corrosive Sulphur – DIN 51353 Pass
Water Content on Delivery ppm IEC 60814 9
Oil Quality Index (OQIN) – – 4400
Oxidation Stability h IEC 61125 Report
Gassing Tendency mm³/min ASTM D2300 Report
Furfural Content ppm IEC 61198 Report