Description
Inhibited Transformer Oil INH-T2 – 5L (Service/Top-Up Pack)
Premium inhibited transformer oil 5l for professional service work and top-ups. Meets IEC 60296:2020 (Inhibited). The product is PCB-free and has been Eskom tested (meets Eskom required parameters; pending final Eskom Approval).
Benefits at a glance
73 kV dielectric strength (before treatment)
−47 °C pour point for cold-start reliability
Low moisture on delivery (9 ppm typical)
Non-corrosive; copper and sulphur tests pass
Typical Physical Characteristics (TDS)
Property Units Test Methods Typical Data
Visual Appearance – – Clear, Pale
Kinematic Viscosity @ 40 °C mm²/s ISO 3104 8.2
Viscosity Index – ASTM D2270 115
Flash Point (COC) °C ISO 2719 178
Pour Point °C ISO 3016 −47
Density @ 20 °C kg/m³ ISO 12185 0.828
Breakdown Voltage (before treatment) kV IEC 60156 73
Dissipation Factor (DDF) @ 90 °C – IEC 61156 <0.11
Resistivity @ 90 °C TΩ·m IEC 60247 >10
Interfacial Tension mN/m ASTM D971 44
Acidity mg KOH/g IEC 62021 0.01
Inhibitor Content W% IEC 60666 0.4%
Aromatic Content % IEC 60590 12
PCB Content – IEC 61619 Not Detectable
Corrosive Copper – ASTM D1275 Pass
Corrosive Sulphur – DIN 51353 Pass
Water Content on Delivery ppm IEC 60814 9
Oil Quality Index (OQIN) – – 4400
Oxidation Stability h IEC 61125 Report
Gassing Tendency mm³/min ASTM D2300 Report
Furfural Content ppm IEC 61198 Report
Pack size: 5L. Also in 1L, 20L and 210L.





Reviews
There are no reviews yet.